Radiator BTU Calculator

Calculate the BTU and wattage needed for your radiators based on room size, glazing and external walls.

Source: Zehnder — Delta T correction factors

Konstantin Iakovlev

By Konstantin Iakovlev · Founder, Calks.uk

Last updated: · Correction factors from published radiator data, 2026; sizing is a rule of thumb

BTU Required

9,547

Watts Required

2,798 W

Room Volume

48.0 m³

Catalogue ratings are at ΔT50, so compare this figure with them directly. If your radiators run cooler than that, choose a lower water temperature above.

Disclaimer

This calculator is for guidance only. Confirm quantities with your supplier before ordering, and use a qualified tradesperson for structural work. Rates and figures come from published radiator data from Zehnder and QS Supplies and are reviewed for 2026. Everything is calculated in your browser; nothing you enter is sent to our servers.

How It Works

Radiator sizing is calculated in BTU/h (British Thermal Units per hour). A BTU is the energy needed to raise 1 lb of water by 1°F, and UK radiators are rated in BTU/hour or in watts, where 1 BTU/hr = 0.293 W and 1 kW = 3,412 BTU/hr. The base calculation multiplies room volume (length × width × height in metres) by a base factor: 153 BTU per m³ for a living room or kitchen, 133 for a bedroom, 170 for a bathroom and 136 for a hallway. The calculator then adjusts for external walls and glazing. The aim is to estimate the heat the room loses, then choose radiators whose combined output matches or slightly exceeds it.

The calculator adds 15% for each external wall and 20% for single glazing, and takes off 10% for triple glazing. For a 5 m × 4 m × 2.4 m living room, the volume is 48 m³, the base figure is 48 × 153 = 7,344 BTU/h, and two external walls multiply that by 1.30 to give 9,547 BTU/h. Double glazing needs no adjustment, so radiators totalling about 10,000 BTU/h would suit. With no external walls the same room needs 7,344 BTU/h, and with four it needs 11,750 BTU/h. Rules of thumb also allow extra for rooms above a garage or unheated space, north-facing rooms, solid walls and large windows, none of which the calculator includes, while ceiling height is already counted through the volume. Bathrooms typically require a higher target temperature (22°C versus 21°C for living rooms).

Enter the room dimensions and characteristics and the calculator shows the total BTU/h and watts requirement, plus the catalogue rating to look for if your radiators run cooler than the standard. Most UK radiator manufacturers publish outputs at Delta T50, which means a 20°C room and water averaging 70°C, such as 80°C flow and 60°C return. Older catalogues used Delta T60, the UK standard until 2013, which looks higher: multiply a Delta T60 figure by 0.787 to compare it. A boiler turned down to a 50-60°C flow runs well below Delta T50. At 55°C flow and 45°C return the water averages 50°C, which is Delta T30, and a radiator gives only about 51% of its rating, so a 1,700W radiator delivers about 870W. If your system runs at a lower flow temperature still (for example with a heat pump), the output falls further.

Radiator type matters as much as size. A single panel (Type 11) has a low output and a slim profile, a double panel with a single convector (Type 21) sits mid-range, and a double panel with double convector (Type 22) gives the highest output but is deeper. At 1,000mm × 600mm and 50°C ΔT, a Type 11 produces 920W (3,140 BTU/hr) while a Type 22 produces 1,700W (5,800 BTU/hr), so the same wall space can deliver close to double the heat. Fit a thermostatic radiator valve (TRV) on every radiator so that each room can be controlled individually.

Heat pumps change the sums. They deliver heat at a 35-45°C flow temperature, against the 70-80°C a gas boiler has traditionally been set to, so a radiator sized at Delta T50 will not deliver its rated heat. At 45°C flow and 35°C return the water averages 40°C, which is Delta T20, and a radiator gives about 30% of its rating, so a double panel rated at 1,500W delivers roughly 450W. To heat the same room, the catalogue rating has to be about 2.4 times the requirement at Delta T25 and over 3 times at Delta T20. A retrofit therefore means replacing radiators, adding fan-coil units or installing underfloor heating. The Boiler Upgrade Scheme grant of £7,500 requires sufficient heat emission, and the installer's survey assesses radiator sizing as part of that.

For quick estimates, a 4 m² bathroom needs about 2,500 BTU from a heated towel rail, a 12 m² kitchen 5,000-6,000 BTU, an 18 m² lounge 6,000-8,000 BTU and a 14 m² double bedroom 5,000-6,000 BTU. A TRV can only hold a radiator back, not push it beyond what it gives at your water temperature. A radiator 10-20% short may need a longer warm-up and can fall short on the coldest days, and a badly under-specified one never gets the room to its target temperature. Over-specifying costs more up front, but the TRV can trim any surplus.

Example: Living room 5 m × 4 m × 2.4 m, 2 external walls, double glazing

  1. Volume: 5 × 4 × 2.4 = 48 m³
  2. Base BTU: 48 × 153 = 7,344 BTU/h
  3. Two external walls (+15% each): × 1.30 = 9,547 BTU/h
  4. Double glazing (no adjustment): 9,547 BTU/h
  5. Recommended: radiator(s) totalling ~10,000 BTU/h

Source: Zehnder — Delta T correction factors

Frequently Asked Questions

How is the BTU size of a radiator worked out?
The starting figure comes from room volume (length times width times height in metres) multiplied by a base factor, 153 BTU per cubic metre for a living room. That base is then adjusted for external walls and glazing. A 48 m³ living room starts at 7,344 BTU/h and rises to 9,547 BTU/h once two external walls are counted at 15% each.
How do I convert radiator BTU to watts?
Multiply BTU/hr by 0.293 to get watts, or remember that 1 kW is 3,412 BTU/hr. As a check, a 1,000mm × 600mm Type 11 single panel rated at 920W is 3,140 BTU/hr, and a Type 22 double panel of the same size at 1,700W is 5,800 BTU/hr. Manufacturers list both units, but make sure the figures you compare are all at Delta T50.
What does Delta T50 mean on a radiator?
It is the standard test condition under which UK manufacturers publish outputs, a 50°C difference between the average water temperature and the room, usually water averaging 70°C in a 20°C room. Older catalogues quoted Delta T60, the UK standard until 2013, which looks higher, so multiply those figures by 0.787 to compare. Delta T50 is a basis for comparison, not what you will always get. At 55°C flow and 45°C return a radiator gives about 51% of its rating, and at a heat pump's 45°C flow and 35°C return about 30%.
Will my existing radiators work with a heat pump?
Often not without changes. A heat pump runs at 35-45°C rather than the 70-80°C a gas boiler has traditionally been set to, so a double panel rated at 1,500W drops to roughly 450W at 45°C flow and 35°C return, and the catalogue rating you need is over 3 times the room's requirement. The usual fixes are bigger radiators, fan-coil units or underfloor heating. The £7,500 Boiler Upgrade Scheme grant depends on the installer confirming that heat emission is sufficient, so radiator sizing is checked during the survey.
Is it better to oversize or undersize a radiator?
Slightly oversize. A TRV can trim a surplus but cannot add heat, so a radiator 10-20% under may need longer to warm up and can fall short on the coldest days. Go much further under and the room never reaches temperature. Oversizing costs more up front, so aim for an output that matches or just exceeds the calculated BTU/h figure at your actual water temperature.